faq eurapoHäufig gestellte fragen

Why the fan coil issues an anomalous noise?
  • The filter and/or the coil is clogged
    Clean the filter and/or the coil
  • Vibrations caused by a wrong installation and/or loose fixing screws
    Verify carefully and carry out the corrective actions
  • Unbalanced fan deck
    Replace it
Why the unit does not deliver air?
  • Lack on the power supply.
    Verify the network voltage and/or the integrity of the fuse on the electronic card of the control and the rightness of the electrical connections
  • Set – Point reached.
    Check the control setting.
  • In presence of WS (minimum water temperature thermostat), hot water temperature < 35°C, insufficient water flow and/or temperature in coil, or damaged
    water sensor (WS).
    Check the water temperature and water flow on the coil and/or the correct working of the water sensor (WS).
  • Burnt autotransformer and/or electric fan damaged.
    Replace the damaged components.
Why the air delivered by the unit is not hot or cold enough?
  • Water and/or air temperature at the entry of the fan coil does not comply with the expected values.
    Verify the available power and the installed power. Operate accordingly.
  • The pump is not powerful enough to handle operational requirements.
    Replace the pump with a pump suitable to the installation requirements.